Quote Now


Solutions for Your Industry, Ready for Your Choice

%{tishi_zhanwei}%

How Air-to-Water Heat Pumps Work and Common Problems

Jul 08,2026

Author:

Kadvin

Concept of air-cooled heat pumps: Air-cooled heat pumps combine air-cooled chiller units and heat pump technology, enabling cooling and heating functions within a single system.

Concept of air-cooled heat pumps: Air-cooled heat pumps combine air-cooled chiller units and heat pump technology, enabling cooling and heating functions within a single system. This unit uses external air as a heat source or sink, uses a compression refrigeration cycle, refrigerant as the energy transfer medium, and cooperates with fans for forced air heat exchange, thereby absorbing heat from the air (heating mode) or releasing heat back into the air (cooling mode).

Air-cooled heat pumps do not require dedicated cooling towers or underground pipes or other external water source facilities. Due to their compact structure, flexible installation, and strong adaptability, they are widely used in refrigeration and heating systems in agricultural, commercial, and some light industrial sites.

Air-cooled heat pump working principle

The air-cooled heat pump unit is based on the reverse Carnot cycle (i.e., compression refrigeration cycle), and its main components include a compressor, condenser, throttling device (such as expansion valves or capillary tubes), an evaporator, and a four-way directional valve for switching cooling and heating modes. The work process is as follows:

Cooling mode

○ The compressor draws in low-temperature, low-pressure liquid refrigerant and compresses it into high-temperature, high-pressure gas.

○ The high-temperature, high-pressure refrigerant enters the condenser (acting as a radiator), exchanges heat through the outdoor air introduced by the fins and fan, releasing heat into the air and cooling itself into a high-pressure liquid.

○ After the throttling device lowers the pressure, the liquid refrigerant enters the evaporator (acting as the heat absorber), absorbing heat from indoor return water (or directly with indoor air) and evaporating into low-temperature, low-pressure gaseous refrigerant. The evaporated refrigerant is drawn back into the compressor to start the next cycle.

Heating mode

○ The four-way directional valve operates to change the direction of refrigerant flow, turning the evaporator into the heat absorption end (drawing heat from outdoor air) and the condenser into the heat release end (releasing heat to the indoor water supply system).

○ The rest of the workflow is similar to refrigeration mode, except the heat transfer direction is reversed: the refrigerant draws heat from outdoor air in the evaporator and evaporates it, then compresses it by a compressor into high-temperature, high-pressure gas; In the condenser, the refrigerant transfers heat to the circulating water, which condenses itself into liquid, then passes through the throttling device to reduce pressure before returning to the evaporator to continue absorbing heat.

Common faults and their solutions

Poor cooling performance

Possible causes: insufficient or leaking refrigerant, dirty condenser or evaporator, clogged air filter, severe scaling or dust accumulation in heat exchangers, fan failure, control system failure, etc.

Solution: Check the amount of refrigerant filled, and if necessary, supplement or repair leaks; Regularly clean the condenser and evaporator, replace or clean the air filter; Descaling or cleaning dust accumulated in heat exchangers; Check the fan motor and its drive circuit, repair or replace faulty parts; Verify control system parameters or repair controller faults.

Heating performance declines

Possible causes: inaccurate refrigerant charge, fault of the four-way directional valve, defrosting system failure, low ambient temperature leading to reduced unit efficiency, severe frosting in the heat exchanger, etc.

Solution: Refill or adjust the refrigerant to the specified level, inspect, repair, or replace the four-way directional valve; Check the defrost sensor and control system to ensure the defrosting function is normal; Under extremely low temperature conditions, auxiliary electric heating or other heat sources may be needed; Regular defrosting or optimizing defrosting strategies.

Compressor failure

Possible causes: overload, power supply issues, poor lubrication, internal mechanical wear, high temperatures caused by prolonged operation, etc.

Solution: Check the power supply and voltage stability to ensure compliance with compressor specifications; Regularly replace or replenish lubricating oil to maintain good lubrication; Replace damaged compressor components or the entire machine in a timely manner according to fault indications or professional diagnostics; Set operating parameters reasonably to avoid prolonged full-load operation.

Control system failure

Possible causes: sensor failure, control circuit board damage, software errors, communication failures, etc.

Handling method: Check the accuracy of each sensor's data and replace the faulty sensor; Inspect, repair, or replace faulty control circuit boards; Update control system software to the latest version and fix known software issues; Ensure the communication line is well connected and verify protocol compatibility.

Pump failure or water flow issues

Possible causes: pump motor damage, impeller blockage, water system valve malfunction, pipeline blockage or leakage, etc.

Solution: Check the pump motor and bearings, repair or replace damaged parts; Clean debris from the impeller to ensure smooth water flow; Inspect valves, repair or replace faulty valves; Inspect water system pipelines, repair leaks, or clear blockages.

During maintenance, the unit's operating status should be regularly checked, filters cleaned or replaced in a timely manner, heat exchangers cleaned, refrigerant charge and pressure monitored, and necessary calibrations and software updates for the control system should be performed to ensure long-term stable and efficient operation of the air-cooled heat pump unit. When encountering complex or difficult problems to resolve on your own, it is recommended to contact professional technicians for diagnosis and repair.

 